Network Management Card
– User Manual 34003991EN/EC Page 72/118
6 Configuration via RS232
Use the cord supplied with the card.
Connect the card to a computer equipped with a hyperterminal type emulator. The serial link must be set at 9600
baud, 8 bits, no parity, 1 stop bit, and without flow control.
Check that UPS power is on.
Enter the admin password (not modifiable).
The menu is in English only.
-----------------------------------------------------------------------------
EATON
NETWORK MANAGEMENT CARD
-----------------------------------------------------------------------------
1 : Reset
2 : Network configuration
3 : Set Login Password to Default
4 : Return to Default Configuration
0 : Exit
-----------------------------------------------------------------------------