Network Management Card
– User Manual 34003991EN/EC Page 15/118
Ethernet port
LED Colour Activity Description
ACT Green
Off
Card not connected to the
network.
On
Card connected to the network but
without activity
Flashing
Port is active in receiving /
transmission
100M Orange
Off
Port operating at 10Mbits/s.
On
Port operating at 100Mbits/s.
Service port
LED Colour Activity Description
UPS Green
Off
Card startup in progress.
Data
On
Communication with UPS in
progress
Flashing
Normal operation.
Communication with the UPS is
operational
RS232 Orange
Off
Configuration menu is active
On
Normal operation. Configuration
menu is deactived
Flashing
Communication with the
Environment Sensor (option).
2.3 Installation in the UPS
The Network Management Card (66102) can be "hot" installed in all UPSs of the EATON or Powerware range equipped
with a Minislot without having to shut it down.
Remove the protective plastic cover from the Minislot
Note the card's MAC address prior to insertion
Insert and tighten the card's retaining screws
Connect the ETHERNET cable
Wait 2 min. the card is completely operational when the green UPS Data LED flashes continuously